SERVICE
MANUAL
Tankless Gas Water Heater
Troubleshooting Guide
and Instruction for Service
(To be performed ONLY by qualified service providers)
For the LAARS
®
Heating System
EverHot
®
Exterior Tankless
Gas Water Heater Models:
IGE-199R-10(N,X) IGE-199C-5(N,X)
Document 11014
Save this manual for future reference
Zobrazit stránku 0
1 2 3 4 5 6 ... 59 60

Shrnutí obsahu

Strany 1 - Troubleshooting Guide

SERVICEMANUALTankless Gas Water HeaterTroubleshooting Guideand Instruction for Service(To be performed ONLY by qualified service providers)For the LAA

Strany 2

II - SPECIFICATIONS – GENERAL (cont.)Power Supply Appliance – 120 Volts A.C. – 60 Hz.Remote control 12 volt D.C. (Digital)Safety Devices Flame failur

Strany 3 - Section Description Page

II - SPECIFICATIONS (cont.)COMBUSTION SPECIFICATIONSItem Gas Type Natural PropaneGas Consumption Minimum Btu's 15,000 15,000 Maximum Btu'

Strany 4 - GLOSSARY OF TERMS AND SYMBOLS

12II - SPECIFICATIONS (cont.)DIP SWITCH SETTINGSDANGERDo not attempt to adjust dip switch settings from there factory default settings.Doing so will r

Strany 5 - I - GENERAL INFORMATION

III - MAIN COMPONENTS1. Mechanical Water RegulatorThe unique water regulator mechanism ensures the hot water is maintained with no noticeablechange to

Strany 6

III - MAIN COMPONENTS (cont.)5. Combustion FanAir for the combustion is supplied by a centrifugal fandriven by a DC motor. After a pre-purge period of

Strany 7 - CUT-AWAY ILLUSTRATION

IV - SAFETY DEVICE FUNCTIONFlame FailureSituated to the right of the burner in the front of the combustion chamber, the flame rod monitors thecombusti

Strany 8 - SCHEMATIC ILLUSTRATION

IV - SAFETY DEVICE FUNCTION (cont.)Over temperature Cut-OffThe temperature of the outgoing hot water is constantly monitored by the water temperaturet

Strany 9 - II - SPECIFICATIONS – GENERAL

V - SEQUENCE OF OPERATIONThe preset temperature is selected at one of the remotes controls (where fitted). Where no remotecontrol is fitted , the defa

Strany 10

V - SEQUENCE OF OPERATION (cont.)When the hot water tap is turned off, the water flow sensor stops revolving, and the magnetic pulseceases, indicating

Strany 11 - II - SPECIFICATIONS (cont.)

V - SEQUENCE OF OPERATION (cont.)OPERATION SEQUENCE FLOW CHART19

Strany 12

Key to Warning SymbolsFailure to comply with the following instructions may results in serious personal injury ordamage to the appliance.Be careful of

Strany 13 - III - MAIN COMPONENTS

20V - SEQUENCE OF OPERATION (cont.)OPERATION SEQUENCE FLOW CHART

Strany 14 - III - MAIN COMPONENTS (cont.)

V - SEQUENCE OF OPERATION (cont.)SEQUENCE TIMING CHART21

Strany 15 - IV - SAFETY DEVICE FUNCTION

22V - SEQUENCE OF OPERATION (cont.)SEQUENCE TIMING CHART

Strany 16

23VI - TROUBLESHOOTINGERROR MESSAGESError Faulty Remedy10 Air Supply or Exhaust Blockage Check intake and exhaust ports for obstructions.Check that

Strany 17 - V - SEQUENCE OF OPERATION

24VI - TROUBLESHOOTING (cont.)ERROR MESSAGESError Faulty Remedy32 Outgoing Water Check sensor wiring for damage.Temperature Sensor Faulty Check resi

Strany 18

VI - TROUBLESHOOTING (cont.)QUICK REFERENCE DIAGNOSTIC POINTSIMPORTANT SAFETY NOTES:There are a number of (live) tests that are required when fault fi

Strany 19 - OPERATION SEQUENCE FLOW CHART

VI - TROUBLESHOOTING (cont.)Thermal Fuse:Red ~Red 100 VAC Below 1 ohm B ~C B6 ~C1Overheat Switch:Red ~Red 100 VAC Below 1 ohm B ~C B6 ~C1Flame R

Strany 20

VI - TROUBLE SHOOTING (cont.)Using a voltage meter set to the 200 ohm scale, you should have a resistance reading of 26 - 30ohms through each of thes

Strany 21 - SEQUENCE TIMING CHART

VI - TROUBLE SHOOTING (cont.)WIRING SCHEMATIC28

Strany 22

29Nature of FaultExaminationPoint Diagnostic Point Values Y/N ActionServiceProcedureA. The LED onthe remotecontrol does notlight up, whenthe system is

Strany 23 - VI - TROUBLESHOOTING

TABLE OF CONTENTSSection Description Page- - - Glossary of Terms and Symbols... 4I ...

Strany 24 - VI - TROUBLESHOOTING (cont.)

30Nature of FaultExaminationPoint Diagnostic PointValues Y/N ActionServiceProcedure2. Measure the voltageat connector F withappliance power supplyon.F

Strany 25

31Nature of FaultExaminationPointDiagnostic Point Values Y/N ActionServiceProcedureError code "11"displayed ondigital monitor.5. Check ignit

Strany 26

32Nature of FaultExaminationPoint Diagnostic Point Values Y/N ActionServiceProcedureC. Combustionoccurs, but flamefails.Error code "12"displ

Strany 27 - VI - TROUBLE SHOOTING (cont.)

33Nature of FaultExaminationPoint Diagnostic Point Values Y/N ActionServiceProcedure2. Measure voltagebetween orange (+) andgrey (-) of the water flow

Strany 28

34VI - TROUBLESHOOTING (cont.)Troubleshooting ProcedureUnit’s wiring diagram can be found on page 27.Appliance fails to operate (even remote control f

Strany 29

3) Is the remote control normal?No combustion (despite remote control indication)1) Is the water flow sensor normal?Check voltage between the two remo

Strany 30

362) Is the flame rod normal? Error “72” is displayed3) Is the water temperature thermistor normal?Checking the flame rod.a. # Detach the flame rod t

Strany 31

374) Is the combustion fan motor normal?5) Is the ignition module operating normally?.Check the sparker module.a. Measure voltage at connector F8, gr

Strany 32

38If error “11” or “71” is displayed, check the main gas solenoidvalve.a. # Disconnect the main gas solenoid valve (SV0) connector and measure the re

Strany 33

399) Is the change over solenoid (SV3) operating normally?If error “11” or “71” is displayed, check the change over solenoid (SV3).a. # Disconnect th

Strany 34

GLOSSARY OF TERMS AND SYMBOLSThis glossary of terms and symbols is provided to assist you in understanding some of thelanguage used throughout this ma

Strany 35

40Combustion stops due to flame failure1) Is the flame rod functioning normally?2) Is the earth lead wire connected?a. Measure the voltage between the

Strany 36

41Unable to adjust hot water temperature1) Is the water temperature thermistor operating normally?2) Is the change over solenoid (SV1) normal?a. # Di

Strany 37

42a. # Disconnect the modulating valve festoon C2terminals and measure the resistance at the terminals.Normal: 67 ~81 ΩIf normal, check b.Faulty: Rep

Strany 38

43Anti-frost heaters do not operate1) Are the ceramic anti-frost heaters operating normally?2) Is the frost sensor switch operating normally?a. # Dis

Strany 39

VII - GAS PRESSURE SETTING PROCEDUREAll settings/adjustments must be performedby a qualified Service Technician.1. Turn unit off at power source and

Strany 40

8. Turn off the gas to the water heater. Remove the manometer connection. Reinstall thepressure port plug. Turn on the gas to the water heater and ch

Strany 41

VIII - SERVICE PROCEDURENOTE: Before proceeding with dismantling, be sure to follow the CAUTIONinstructions before each explanation. Always disconnect

Strany 42

47WARNINGDip switched #7 and #8 (combustion control switches) MUSTbe returned to the "OFF" position, after setting pressures.Dip switch #1 M

Strany 43

a. Remove the four (4) Phillips screws that secure the water inlet filter housing to the unit. See picture below for location of screws. Once screws

Strany 44

IGE - 7. Removal of Transformer:CAUTION120 volt potential exposure. Isolate the applianceand reconfirm power has been disconnectedusing a multimeter.a

Strany 45 - Figure #1 Figure #2

I - GENERAL INFORMATIONThis tankless water heater is a high output, high efficiency appliance, which heats the watercontinuously as hot water is being

Strany 46 - VIII - SERVICE PROCEDURE

IGE - 9. Removal of the Gas Valve Assembly:CAUTION120 volt potential exposure. Isolate the applianceand reconfirm power has been disconnectedusing a m

Strany 47

IGE - 11. Removal of Thermal Fuse:CAUTION120 volt potential exposure. Isolate the applianceand reconfirm power has been disconnectedusing a multimeter

Strany 48

IX - FLUSHING PROCEDURE FOR LIMESCALE REMOVAL FROM HEAT EXCHANGERThe amount of calcium carbonate (lime) released from water is in direct proportion to

Strany 49

X - PARTS BREAKDOWNDISASSEMBLED VIEW - CABINET53

Strany 50

X - PARTS BREAKDOWNDISASSEMBLED VIEW - INTERNALS54

Strany 51

X - PARTS BREAKDOWNDISASSEMBLED VIEW - INTERNALS55

Strany 52

X - PARTS BREAKDOWNDISASSEMBLED VIEW - ELECTRICAL56

Strany 53 - X - PARTS BREAKDOWN

PARTS LISTNumber Description Quantity001 Front Panel Assembly 1002 Casing Assembly 1003 Wall Installation Bracket 1004 Connection Reinforcement Panel

Strany 54

715 120v Valve Heater Assembly 1716 Anti-Frost Heater Clip 2717 Anti-Frost Heater Clip A 1718 Anti-Frost Heater Clip 1720 Power Supply Harness 1721 Fu

Strany 55

59Notes

Strany 56

6I - GENERAL INFORMATION (cont.)HOW TO USE THIS MANUALIt is intended for this manual to be used by qualified service personnel for the primary purpose

Strany 57

800.900.9276 • Fax 800.559.1583 (Customer Service, Service Advisors)20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.33551869 Sisme

Strany 58

I - GENERAL INFORMATION (cont.)CUT-AWAY ILLUSTRATION7

Strany 59

I - GENERAL INFORMATION (cont.)SCHEMATIC ILLUSTRATION8

Strany 60

II - SPECIFICATIONS – GENERALType of appliance Temperature controlled continuous flow gas hot water systemOperation With/without remote controlsExhau